Water Supply and Hydraulics

Water Supply Sources

Flow test data, supply curve math, and device losses — everything needed to determine whether a water supply can meet sprinkler system demand.

Interactive tool available

Use the Water Supply Calculator to plot supply curves from flow test data with elevation correction.

Flow test calculation

A fire flow test produces three values: static pressure (no flow), residual pressure (at measured flow), and measured flow (gpm). From these, calculate available flow at any residual pressure using the N^1.85 relationship.

The supply curve formula

The pressure drop from static follows the power-law relationship:

Q_available = Q_measured x [(P_static - P_desired) / (P_static - P_residual)]^0.54

Where:

  • Q_available = available flow at desired residual pressure (gpm)
  • Q_measured = flow measured during test (gpm)
  • P_static = static pressure (psi)
  • P_desired = desired residual pressure (psi)
  • P_residual = residual pressure measured during test (psi)
  • 0.54 = exponent derived from 1/1.85

The exponent 0.54 comes from the Hazen-Williams relationship. Some references use 0.5 as a conservative simplification — this underestimates available flow slightly.

Worked example

Given: Static = 85 psi, Residual = 72 psi at 1,100 gpm. Find available flow at 20 psi residual.

Step 1 — Identify known values:

  • P_static = 85 psi
  • P_residual = 72 psi
  • Q_measured = 1,100 gpm
  • P_desired = 20 psi

Step 2 — Calculate pressure drop ratio: (85 - 20) / (85 - 72) = 65 / 13 = 5.0

Step 3 — Apply the exponent: 5.0^0.54 = 2.38

Step 4 — Calculate available flow: Q_available = 1,100 x 2.38 = 2,618 gpm

Result: Approximately 2,618 gpm is available at 20 psi residual.

Always plot the full supply curve — do not rely on a single calculated point. The curve is nonlinear and real-world conditions may differ from the mathematical model at extreme flows.

Plotting the supply curve

To plot, calculate Q_available at multiple desired residual pressures (e.g., 20, 30, 40, 50, 60, 70 psi) and plot flow (x-axis) vs. pressure (y-axis) on N^1.85 paper or equivalent software.

Desired Residual (psi)Pressure Drop RatioRatio^0.54Available Flow (gpm)
701.151.081,188
601.921.451,595
502.691.751,925
403.462.012,211
304.232.212,431
205.002.382,618
Water supply curve plotted on N^1.85 graph paper showing static pressure, test point, and calculated curve
Supply curve plotted from flow test data. The system demand point must fall below and to the left of this curve.

Elevation correction

Water pressure changes at 0.433 psi per foot of elevation difference. Pressure decreases when the sprinkler system is above the test point and increases when below.

Elevation Change (ft)Pressure Adjustment (psi)Direction
52.17Subtract if above source
104.33Subtract if above source
156.50Subtract if above source
208.66Subtract if above source
3012.99Subtract if above source
4017.32Subtract if above source
5021.65Subtract if above source

Measure elevation from the flow test gauge location to the highest sprinkler in the system, not to the roof or ground floor. Per NFPA 13, adjust both the static and residual pressures at the source.

Device pressure losses

Account for every device between the water source and the sprinkler system when determining available pressure.

DeviceTypical Pressure Loss (psi)Notes
DCDA backflow preventer8-12Double check detector assembly
RPDA backflow preventer12-15Reduced pressure detector assembly
DCVA backflow preventer5-8Double check valve assembly
Alarm check valve5-10Wet system riser
Dry pipe valve5-15Varies significantly by model
Deluge valve5-10Open when activated
Butterfly valve (open)1-3Fully open position
OS&Y gate valve (open)0.5-1Fully open, minimal loss
Compound meterVariesUse manufacturer loss curves for flow rate
Turbine meterVariesUse manufacturer loss curves for flow rate

Always use the manufacturer's published loss data for the specific device model and flow rate. The values above are planning-level estimates only. Backflow preventer losses increase significantly with age and fouling — test annually per NFPA 25.

Safety margin guidelines

The system demand curve must fall below and to the left of the adjusted supply curve with adequate margin.

Authority / StandardMinimum Safety MarginNotes
Typical industry practice10 psiBetween supply curve and demand point
FM Global (Data Sheet 3-0)10 psi or 10% of demandWhichever is greater
Municipal AHJVariesSome require 20% margin
Insurance carrierVariesMay exceed code minimums

Key considerations:

  • Flow test data reflects conditions at the time of the test — municipal pressures fluctuate seasonally and with time of day
  • NFPA 291 recommends testing during peak demand periods for the water utility
  • Supply degradation over time (tuberculation, new development) can reduce available flow
  • Consider future building additions that may increase system demand

Per NFPA 13, Section 27.2 — flow test data more than 12 months old should be verified with the water utility or retested before final design submission.

Water supply adequacy determination

After plotting the supply curve and the system demand point, confirm:

  1. Demand point is below the supply curve at the required flow rate
  2. Safety margin meets the AHJ and insurance requirements
  3. Elevation corrections are applied from the test point to the highest sprinkler
  4. All device losses are subtracted from the supply side
  5. Hose stream demand is added per NFPA 13 Table 11.2.3.1.2

If the supply is inadequate, options include: fire pump (see Fire Pumps), dedicated water storage tank (see Water Storage Tanks), or connecting to a second water main.

Previous
Home